What is PUE, how is it calculated and why does it matter?

PUE, the key metric of data center energy efficiency: how it is calculated, what a good value looks like and the methods used to lower it.

By: Energy & Sustainability Team

Isometric view of the FRA-1 campus: data halls, rooftop chillers, generator yard, substations and fiber entrieskaledatacenterFRA-1Free-cooling chillers10 × chillers · N+1Generator yard2N+1 · 72 hours of fuelSubstations A / BTwo separate 154 kV linesFiber entry 1 / 2Diverse routesData halls4 halls · 6 MW IT load

PUE (Power Usage Effectiveness) is the ratio that shows how much of the total energy a data center consumes actually reaches IT equipment. The formula is simple, but measuring it correctly is harder than it looks.

The formula

PUE = total facility energy ÷ IT equipment energy. The theoretical ideal is 1.0, meaning all energy goes to servers, storage and network devices with no losses to cooling, lighting or power conversion.

What is a good PUE?

The industry average has hovered around 1.5 for years. In new-generation facilities, below 1.3 is considered good and below 1.2 very good. Our facilities averaged 1.24 in 2026; our 2030 target is 1.20 across all locations.

How should it be measured?

Spot measurements can be misleading: PUE measured on a cold winter night is far lower than on a summer afternoon. When comparing, ask for at least a twelve-month average and where the measurement is taken (UPS output, PDU or server input).

Ways to lower PUE

  • Hot or cold aisle containment to prevent air mixing
  • Free cooling: compressor-free cooling when outside temperatures allow
  • Higher hall temperatures: 24–27 °C within ASHRAE recommendations
  • High-efficiency UPS and transformers to reduce conversion losses
  • Liquid cooling: carrying heat with water instead of air in high-density racks

PUE alone is not enough

A low PUE says nothing about where the energy comes from. That is why we report PUE together with the renewable energy share, water usage effectiveness (WUE) and carbon intensity, broken down by location in our annual sustainability report.